ABB MS11625 Starter Motor
Brand: ABB
P/N: MS116-25
14
People watching this product now!
Fast Shipping
Carrier information
20k products
Payment methods
24/7 Support
Unlimited help desk
2-day Delivery
Track or off orders
Description
ABB MS11625 Starter Motor
ABB MS11625 Starter Motor
- Extended Product Type: MS116-25
- Product Description: MS116-25 Manual Motor Starter
- Product Net Width: 45 mm
- Product Net Height: 97.8 mm
- Product Net Depth / Length: 85.4 mm
- Long Description: This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. It offers a rated service short-circuit breaking capacity Ics = 10 kA at 400 VAC and trip class 10A. It is suitable for three- and single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.
MS116-25 Product Specification:
- Rated Service Short-Circuit Breaking Capacity (Ics):
- (230 V AC) 10 kA
(400 V AC) 10 kA
(440 V AC) 3 kA
(500 V AC) 3 kA
(690 V AC) 2 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
- (230 V AC) 16 kA
(400 V AC) 16 kA
(440 V AC) 15 kA
(500 V AC) 10 kA
(690 V AC) 3 kA
- Rated Instantaneous Short-Circuit Current Setting (Ii):
- 375 A
- Setting Range:
- 20 … 25 A
- Rated Operational Power AC-3 (Pe):
- (400 V) Three Phase 11 kW
- Rated Operational Power AC-3e (Pe):
- (400 V) Three Phase 11 kW
- Rated Operational Voltage:
- Main Circuit 690 V AC
- Rated Operational Current (Ie):
- 25 A
- Rated Operational Current AC-3 (Ie):
- 25 A
- Rated Operational Current AC-3e (Ie):
- 25 A
- Rated Frequency (f):
- Main Circuit 50 Hz
Main Circuit 60 Hz
- Rated Impulse Withstand Voltage (Uimp):
- Main Circuit 6 kV
- Rated Insulation Voltage (Ui):
- 690 V
- Power Loss:
- at Rated Operating Conditions per Pole 1.8 … 2.8 W
- Number of Poles:
- 3
- Conventional Free-air Thermal Current (Ith):
- Main Circuit 25 A
- Degree of Protection:
- Housing IP20
Main Circuit Terminals IP10
- Pollution Degree:
- 3
- Electrical Durability:
- 50000 cycle
- Mechanical Durability:
- 100000 cycle
- Terminal Type:
- Screw Terminals
- Connecting Capacity Main Circuit:
- Flexible with Ferrule 1/2x 0.75 … 6 mm²
Flexible with Insulated Ferrule 1/2x 0.75 … 6 mm²
Flexible 1/2x 1 … 2.5 mm²
Flexible 1/2x 2.5 … 6 mm²
Rigid 1/2x 1 … 2.5 mm²
Rigid 1/2x 2.5 … 6 mm²
- Tightening Torque:
- Main Circuit 2 N·m
- Wire Stripping Length:
- Main Circuit 10 mm
- Recommended Screw Driver:
- Pozidriv 2
- Mounting Position:
- 1 … 6
- Mounting on DIN Rail:
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Minimum Mounting Distance:
- Electrical Conductive Board, Horizontal – Up to 400 V 0 mm
Electrical Conductive Board, Horizontal – Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
- Contact Position Indication:
- ON / OFF
- Actuator Type:
- Rotary Handle